Bộ Lưu Điện ECOs 1 Pha Online-Rack/Tower 2KVA
- [Download Catalogue]
- Bộ Lưu Điện ECOs 1 Pha Online-Rack/Tower 2KVA
Thông tin tổng quan Bộ Lưu Điện ECOs 1 Pha Online-Rack/Tower 2KVA
Thông số kỹ thuật Bộ Lưu Điện ECOs 1 Pha Online-Rack/Tower 2KVA
Model | EC2K1 |
Capacity | 2kVA / 1800W |
Input | |
Rated voltage | 208V / 220V / 230V / 240 Vac |
Voltage range | 110 ~ 176 Vac (linear derating between 50% and 100% load), 176 ~ 280Vac (no derating), 280 ~ 300Vac (derating 50%) |
Frequency | 50 – 60Hz (auto sensing) |
Power factor | ≥ 0.99 |
Bypass voltage range | -25% ~ +15% (settable) |
Total harmonic distortion (THDi) | ≤ 6% |
Generator connection | Yes |
Output | |
Voltage | 1 phase 208V / 220V / 230V / 240 Vac (settable via LCD) |
Voltage regulation | ± 1% |
Frequency | Synchronized range; 50/60Hz± 0.05Hz (in battery mode) |
Waveform | Pure sin wave |
Power factor | 0.9 |
Total harmonic distortion (THDi) | < 2% (linear load); < 5% (non-linear load) |
Crest factor | 3:1 |
Overload / Overload protection | 105% ~ 125% for 1 min, 125% ~ 150% for 30 sec, > 150% for 300 ms auto transfer to bypass when overload > 150% and fault then shutdown |
Socket | Universal *2 / IEC C13*4 |
Batteries | |
DC voltage / Type | 48VDC / VRLA Valve regulated sealed lead-acid maintenance free battery |
Inbuilt battery | 12V * 9Ah * 4 |
Backup time at full load | 4 ~ 6 mins |
Recharge time | Standard mode: 90% capacity restored in 5 hours |
Advanced battery management (auto transfer to continuous charging); Prioritize slow charging to preserve battery life |
|
System | |
Efficiency | ≥ 90% (Inverter mode) |
Transfer time | Main mode to battery mode: 0ms | Inverter mode to bypass mode: 4ms (typical) |
Protections | Short circuit, overload, over-temperature, battery discharge protection and fan testing protection |
Communications | RS232 (standard) with management software-UPS monitoring viva RS232 connection; Optional for USB / RS485/ dry contacts / EPO / Intelligent slot use for NMC / SNMP / CMC modbus / AS400 card |
LCD + LED display | UPS operating status by LCD (Load, battery, input, output, charging, discharging, fault…) |
Others | |
Operating / Storage temperature | 0° ~ 40°C / -25° ~ 55°C (without batteries) |
Relative hudmity | 20 ~ 95% (non-condensing) |
Noise level at 1m | < 50 dB (1m) |
DOCUMENTATION
- Please approach our authorized dealer/distributor for details.
- This data may be revised without prior notice. All pictures shown are for illustration purpose only.